404A Pressure Temperature Sample Chart

404A Pressure Temperature Sample Chart

°FR‐404A
‐500.6
‐452.7
‐405
‐357.6
‐3010.4
‐2513.4
‐2016.8
‐1520.5
‐1024.5
‐528.8
033.5
538.6
1044
1549.9
2056.2
2563
3070.3
3578.1
4086.4 SYSTEM PROBLEM DISCH PRESS SUCT PRESS SUPERHEAT SUBCOOLING AMP DRAW
4595.2 OVERCHARGEHIGH\\HIGHHIGH
50104.7 UNDERCHARGE\LOWHIGH\\
55114.7 LIQUID RESTRICT.\LOWHIGH\LOW
60125.3 LOW EVAP FLOW\LOWLOW\\
65136.6 DIRTY CONDENSERHIGH\\\HIGH
70148.6 LOW AMBIENT °FLOW LOWHIGHHIGH\
75161.2 TXV BULB BAD\LOWHIGH\\
80174.6
85188.8
90203.7
95219.4
100235.9
105253.4
110271.7
115290.9
120311.1
125332.3
130354.5
135377.8
140402.2
145427.7
150454.4
Subcooling is determined by taking the high side pressure gauge reading, converting that
pressure to temperature using a PT chart, and then subtracting that temperature from
the actual temperature measured (using an accurate thermometer or thermocouple) at
the same point the pressure was taken.
404A PRESSURE‐TEMPERATURE CHART
REFRIGERATION SYSTEM ANALYSIS
WHAT IS SUPERHEAT & SUBCOOLING AND HOW TO MEASURE IT
Superheat refers to the number of degrees a vapor is above its saturation temperature
(boiling point) at a particular pressure.
Superheat is determined by taking the low side pressure gauge reading, converting that
pressure to temperature using a PT chart, and then subtracting that temperature from
the actual temperature measured (using an accurate thermometer or thermocouple) at
the same point the pressure was taken.
Subcooling is the condition where the liquid refrigerant is colder than the minimum
temperature (saturation temperature) required to keep it from boiling and, hence,
change from the liquid to a gas phase.